This guide treats PCD235 A101 · 3BHE032025R0101 and PCD235 C101 · 3BHE057901R0101 as separate purchasing references. A shared family name or R0101 suffix does not prove that one can replace the other.
ABB's published PC D235 A datasheet documents A101; it does not establish a general A101/C101 substitution. C101 specifications must be checked against the installed system and applicable ABB documentation.
Open the model record before requesting a quote
The installed nameplate is the starting point. Record the complete order code, A101 or C101 marking, hardware revision, serial number, cabinet position and quantity. On paired equipment, record both positions independently.
Documented ABB A variantPCD235 A1013BHE032025R0101
ABB identifies this as an AC 800PEC CIO-FU combined input/output device. Its published interfaces include:
- 12 digital inputs and 16 relay outputs
- 3 analog inputs and 3 analog outputs
- 3 PT100/PTC temperature interfaces
- Optical links and isolated RS-485 interface
These counts apply to A101 only. Use the ABB-authored datasheet and the site configuration when preparing tests.
Verify against installed recordsPCD235 C1013BHE057901R0101
Request this complete identifier as a separate quotation line. Do not copy A101 channel counts or internal-board details into the C101 purchase specification without C101-specific evidence.
If a supplier offers A101 for an installed C101, hold the order until the plant's responsible engineer has reviewed documented compatibility, wiring, settings and test requirements.
Do not turn every excitation alarm into a complete-device order
For an installed PCD235 A101, ABB's interface list helps define which evidence should accompany an RFQ. The checks below are planning prompts for qualified personnel following site procedures—not live-work instructions.
Review the 24 V supply path, device address, status indication and upstream diagnostics.
RFQ evidence
Alarm history, nameplate and cabinet position.
Identify the affected input group, field contact, wiring and polling supply.
RFQ evidence
Channel list and the observed fault, not only “bad PCD235.”
Check the affected channel, configured signal type, terminal and field device.
Acceptance test
Verify that specific measurement or command path.
Identify the PT100/PTC sensor type, wiring and corresponding interface.
Acceptance test
Test the affected temperature path after replacement.
Review the optical link, isolated RS-485 path and connectors.
Supply scope
Confirm any required optical or connector components.
ABB says two PC D235 A devices can support redundant system interfaces. This does not mean every installation uses redundancy or that a device can be hot-swapped. Confirm the site's approved architecture and procedure. Source: ABB PC D235 A datasheet.
“Available” does not tell you what will arrive
The A101 datasheet identifies internal components including PD D205 A, UC D208 A, KU D210 A and UF D202 A. If the outage plan requires a complete PC D235 device, a quotation for one internal board is not the same supply scope. ABB source.
Request written confirmation of:
- The full order code and A101/C101 marking on the actual unit
- Hardware revision and any additional nameplate identifiers
- Complete assembly versus a specified board or subassembly
- Included optical-interface parts, connectors and accessories
- Condition, testing performed, warranty and committed dispatch date
Keep adjacent UNITROL references on separate RFQ lines
Is the spare ready for the outage?
Use these four on-screen checks to organize the handoff between engineering, purchasing and maintenance. They are not a substitute for the plant's formal sign-off.
Checklist selections are only for this browser view and are not saved or sent to Moore.
ABB's excitation-service information treats hardware/software versions, ABB reference numbers and on-site quantities as inputs to spare-parts assessment. Critical spare boards may also be scheduled for health and functional checks. ABB Excitation Care reference.
Subject: ABB PCD235 spare for planned outage
Installed part: PCD235 A101 / 3BHE032025R0101 OR PCD235 C101 / 3BHE057901R0101
Attach: actual nameplate + connector photos; cabinet position; quantity
Confirm: offered revision; complete assembly or subassembly; condition; tests; warranty; delivery date
Rule: do not quote A101 as a C101 substitute without documented approval.
Recommended ABB models to keep on separate inquiry lines
Use the arrows to review related excitation and control references. These cards are sourcing references, not interchangeability claims; verify every complete order number, revision, system position and supply scope.
FAQ: click a question to open the answer
Can PCD235 A101 directly replace PCD235 C101?
Do not assume it can. The complete order numbers differ, and the A101 datasheet does not provide a general A101-to-C101 replacement approval. Obtain an installation-specific engineering decision.
Both numbers end in R0101. Does that make them the same?
No. The suffix is only part of each complete ordering code. Match the entire number and the A101 or C101 designation on the actual nameplate.
Why specify “complete assembly” for 3BHE032025R0101?
ABB documents multiple internal components in PC D235 A101. A quotation for one internal board must not be treated as a quotation for the complete device. Ask for a written scope and actual-item photos.
Does one abnormal A101 input require replacing the full device?
Not necessarily. Under approved site procedures, first review the field contact, wiring, polling supply and diagnostics for the affected channel before deciding the replacement scope.
Is Moore's PCD230 A101 a PCD235 alternative?
No such substitution is supported by the cited ABB list. PC D230 is listed as a CCM module, whereas PC D235 A is a CIO device. Treat them as separate RFQ lines.
Is a stock photo enough to schedule installation?
No. Request photos of the actual offered unit with the full code and revision visible, then confirm its scope and inspect the delivered hardware before release.
What belongs in an urgent PCD235 RFQ?
Send the installed nameplate and connector photos, full number, quantity, cabinet position, system details, required assembly scope, acceptable revision criteria and outage date. Flag any proposed substitute for engineering approval.
What should be verified when the PCD235 spare arrives?
Compare the delivered unit with the approved purchase record: full order code, A101 or C101 marking, hardware revision, assembly scope, condition and included accessories. Hold it from outage release if any item differs.
Send the nameplate to Frida before the outage window closes
Ask Frida for separate quotations for 3BHE032025R0101 PCD235 A101 and 3BHE057901R0101 PCD235 C101 as needed. Include installed-unit photos and ask Moore to confirm the actual offered revision, supply scope and delivery date.